Inquiry

Contact Form

Boiler for Industrial

Boiler for Industrial, Find Details and Price about Hot Water Boiler Biomass Fired from Boiler for Industrial.

Model NO:DZL/SZL/WNS/SZS
Function:Water Boiler, Steam Boilers
Fuel:Coal-Fired
Installation:Packaged Boiler
Structure:Fire Tube
Media:Steam
Water Circulation:Forced Circulation
Drum Placement:Horizontal Boiler
Pressure:Low Pressure
Manufacturing Level:A
Burning Style:Chamber Combustion Boiler
Usage:Industrial
Trademark:QD Hammer
Transport Package:Naked by 40′ Ot or Flat Rack Containers
Origin:Qingdao
HS Code:84021900

Basic Info:

US$10,000.00-200,000.00 / Piece FOB Price:
1 Piece Min. Order:
Qingdao, China Port:
10sets/Month Production Capacity:
L/C, T/T, Western Union, Paypal, Money Gram Payment Terms:
84021900 HS Code:

Category & Tag:

Boiler for Industrial

DZL Series Hot Water Boiler Specification
The DZL series easy installation steam boiler is the most advanced water-fire
tube boiler in China, which is strong, high efficiency, but with small
installation space, long life.
The ameliorated boiler uses the wing smoke flue, one-way threaded smoke pipe,
arch tube sheet, smoke-gas segregation room, and several other advanced
technologies so that the boiler bearing condition could be ameliorated, the
circulating water flow speed could be improved and the safety coefficient could be enhanced.
This series boiler is well designed, compactly made-up, quickly installed, mono layer, so that the civil engineering and the investment could be saved. This amelioration, which extends the boiler’s working life and is the national energy saving product, makes great contribution to the further development of boiler, it sets the pace in china and fill up the national margin.

   Boiler ModelDZL1.4-0.7/95/70-AIIDZL2.8-0.7/95/70-AIIDZL4.2-1.0/
115/70-AII
DZL5.6-1.0/
115/70-AII
DZL7.0-1.0/
115/70-AII
DZL14-1.25/
115/70-AII
Rated Evaporation CapacityMW1.42.84.25.67.014
Operation PressureMpa0.70.71.01.01.01.25
Steam TemperatureºC9595115115115115
Water-inlet TemperatureºC707070707070
Boiler Heating Efficiency%≥76.6≥78.8≥79≥82≥82≥83
Area of StokerM23.045.147.411.411.420.8
Coal AvailableII type bitumite, low heat capability:17700-21000KJ/kg
Water PumpModelIS80-65-160IS100-80-160IS125-100-200IS125-100-200IS125-100-200IS125-100-250
Motor PowerKW7.51530455575
Blast FanModelG6-41-13
NO5.4A
G6-41-13
NO6.4A
G6-41-13
NO7.1A
G6-41-13
NO8.5A
G6-41-13
NO8.5A
TG20-1
Ventilationm3/h4358-23107358-359610354-539418137-936918137-936732079
Wind PressurePa994-12541181-14361697-22702535-33912535-33912559
Motor PowerKW35.57.518.518.537
Induced Draft FanModelY6-41-13
NO5.4C
Y6-41-13
NO7.1C
1Y6-41-13
NO10C
Y6-41-13
NO11.2D
Y6-41-13
NO11.2D
GY20-15
Ventilationm3/h8901-435015219-817132144-1660741773-2157841773-2157873308
Wind PressurePa2568-32402454-32832574-34442764-36972764-36973515
Motor PowerKW1122374555110
Dimensions of Biggest Parts for ShipmentM5.82×2.26×3.226.51×2.6×3.527.5×2.9×3.57.1×3.2×3.57.5×3.2×3.59.1×2.4×3.55
Weight of Biggest Parts for ShipmentT192835374030

Remark: This parameter is just for reference, for exact parameter, suject to our drawings.

SZL Series Hot Water Boiler Specification
SZL water tube easy installation(assembled) boiler has 2 vertical steam drums, and the
innovative horizontal cyclone-fired combustion chamber, which could effectively enhance
the thermal efficiency and reduce the flue gas emission concentration. The flue gas emission
concentration is lower than 100 mm/nm3, the flue gas blackness is lower than Ringelmann
level 1,which enables the boiler to be used in the first-class environment protected area.
The boiler installs one cast iron economizer at its back body, the fire-gate applies the
chamber-segregated ventilation structure, which is easy to adjust. The separate-layer coal
supply device could be chosen according to the customer requirement. Advantages of
such boiler are: strong power, high thermal efficiency, 110% override capability,
compactly designed, small floor area.

Boiler ModelSZL4.2-1.0/
95/70-AII
SZL5.6-1.0/
95/70-AII
SZL7.0-1.0./
115/70-AII
SZL10.5-1.25/
115/70-AII
SZL14-1.25/
130/70-AII
Rated Evaporation CapacityMW4.25.67.010.514
Operation PressureMpa1.01.01.01.251.25
Steam TemperatureºC9595115115130
Water-inlet TemperatureºC7070707070
Heating Efficiency%≥80≥80≥80≥81≥82
Area of StokerM27.158.611.7216.418.9
Coal AvailableII type bitumite,low heat capability:17700-21000KJ/kg
Water PumpModelIS125-100-
200
IS125-100-
200
IS125-100-
250
IS125-100-
250
IS200-150-
315
Motor PowerKW3045557575
Blast FanModelG6-41-13
NO7.1A
G6-41-13
NO8.5A
G6-41-13
NO8.5A
TG15-1TG20-1
Ventilationm3/h5349-103549369-181379369-181372300032079
Wind PressurePa1697-22702535-33912535-339119602559
Motor PowerKW7.518.518.52237
Induced Draft FanModelY6-41-13
NO10C
Y6-41-13
NO11.2D
Y6-41-13
NO11.2D
TY15-2GY20-15
Ventilationm3/h32144-
16604
41773-
21578
41773-
21578
4000073308
Wind PressurePa2575-34442764-36972764-369730383515
Motor PowerKW37454575110
Dimensions of Biggest Parts for ShipmentM7.62×3.27×
3.46
8.82×3.34×
3.46
8.0×3.5×2.79.05×3.35×
3.69
10.6×3.35×
3.69
Weight of Biggest Parts for ShipmentT3145282427

Company Info